XD 1 N series
Multi-channel temperature control module
User manual
User manual
XD 1 N series
Multi-channel temperature control module
User manual
User manual
Preface
This manual describes the XD1N series multi-channel temperature control module, including installation, performance, and usage.
When using the XD1N multi-channel temperature control module, the following precautions should be observed:
• Allow specialists with extensive knowledge of electrical systems to operate the temperature control module .
• Read this manual completely and make sure you understand it before attempting to use the temperature control module
content and use the temperature control module correctly according to the information provided.
• Keep this manual in a safe place for future reference.
Thank you for choosing Xianda products. Please read this instruction carefully before use and keep it properly for reference when needed. If you have any questions, please call the nearby dealer or our company's technical support hotline.
Wiring warning
• If a module fails or an error occurs, it can cause system failure. Install external protection circuits to prevent such accidents .
• To prevent module damage or failure, use fuses to protect power lines and output lines to prevent strong current from impacting the power supply.
• To prevent module damage or failure, please use rated power supply
• To prevent module damage or failure, please power on after completing the wiring work and checking that it is correct.
Restrictions on use occasions
• To prevent fire, it is prohibited to use it in places with flammable and explosive gases.
• To prevent module damage, please do not use the module in places with corrosive gas or steam emissions
• To prevent module damage, please do not use the module in places subject to strong vibrations and impacts .
• This product should not be used in situations where the failure of the controller may cause personal safety accidents or cause significant property damage. If necessary, independent protection measures should be designed and installed around the periphery.
User manual
non-commitment part
|
|
|
|
Safety precautions
Notice | |
| |
| |
| |
| |
| |
| |
|
User manual
|
The following precautions must be observed to prevent operational failure, malfunction, or adverse effects on product performance and functionality. Otherwise, unexpected events may occur.
1)
This product is for indoor use only. Do not use outdoors or in one of the following locations:
·
Places directly exposed to heat radiation from heating equipment
·
Places with liquid splash or oily air
·
Direct sunlight
·
Where there is dust or corrosive gas (especially sulfur gas or ammonia gas)
·
Places with drastic temperature changes
·
There is ice or condensation
·
Place subject to vibration or strong impact
2)
Use and store this product within the rated ambient temperature and humidity range.
Installing two or more temperature sensors close to each other or installing temperature control modules on top of each other will cause heat to accumulate inside the temperature control module, shortening its service life. if
If the temperature control module is to be installed close to or stacked on top of each other, a fan should be used for forced cooling or other measures should be taken to cool down the temperature control module.
3)
To facilitate heat dissipation, do not block the area around the product and do not block the vents on the product.
4)
Pay attention to the terminal polarity when wiring.
5)
Please use pin-type terminals with a crimped front end smaller than 2.35mm in diameter. Do not use excessive force when locking the terminals, and make sure the wiring is connected to the correct terminal.
6) Do not use terminals without specific purposes.
7)
To reduce induced noise, keep wiring to the product's terminal block away from cables carrying high voltages or currents. Likewise, do not connect power cords in series or parallel with product wiring. It is recommended to use shielded cables and use separate conduits.
Install a surge suppressor or noise filter on peripheral devices that produce noise (especially motors, transformers, solenoids, solenoids, or other devices with inductive components).
If a noise filter is used at the power supply, first check the voltage or current and install the noise filter as close to the product as possible.
Leave sufficient space between this product and equipment that generates powerful frequencies (high-frequency welders, high-frequency sewing machines, etc.) or equipment that generates surges.
8)
Use this product with rated load and power supply.
9)
Use switch or relay contacts to ensure rated voltage is reached within 2 seconds after turning on power. If voltage is applied slowly, the power supply may not reset or may
malfunction occurs.
10)
Make sure to preheat before starting actual control operations after turning on the power to ensure the correct temperature is displayed.
11)
The switch or circuit breaker must be placed within easy reach of the operator and must be marked as the disconnecting means for the unit.
12)
Do not use paint thinner or similar chemicals to clean this product. Use standard alcohol.
13)
When designing a system (such as a control panel), allow for a delay in the relay before the output takes effect after the product is powered on.
14)
Never touch electronic components, connectors, or patterns on product panels with bare hands. This product should be held by its outer shell. Improper handling of this product may
Internal parts may be damaged by static electricity.
15) Use switches, relays or other devices with contacts to quickly turn off the power supply. Gradually reducing the power supply voltage may cause erroneous output or memory errors.
16)
Do not touch electronic components with your hands or subject them to shock when removing the terminal block.
17)
Only connect the specified number of this product in the specified configuration.
18)
Install this product on a DIN rail vertical to the ground .
19)
Power must be turned off before wiring the product, replacing the product, or changing product configurations.
20)
During installation, install the included cover over the left open connector on the terminal unit.
User manual
Version revision history
| | |
V2.0 | | 2022-01 |
User manual
General catalog
Table of contents
1-2-2 indicator light definition 14
1-3 I/O configuration and main functions 15
1-3-3 Electrical indicators 16
1-5-1 Ordering Guide (Example) 18
Chapter 2 Hardware and Software Introduction 19
2-3-1 Operating environment 23
2-3-2 Software installation 23
2-4-3 Communication settings 27
2-4-3-1 RS485 communication parameter setting 27
2-4-3-2 Ethernet communication parameter setting 29
2-5 Expansion module internal communication station address automatic allocation 32
2-7-2 Basic parameter setting 39
2-7-5 Control parameter setting 42
2-7-6 LSP group parameter setting 43
2-7-7 PID group parameter setting 44
2-7-10 RS485 communication station number setting 48
2-7-10-1 RS485 communication station number 48
2-7-11 Ethernet IP address setting 50
Chapter 3 Typical Control Cases 54
3-1 Typical single module control configuration 55
3-1-3 Communication settings 56
3-1-4 Module parameter setting 57
3-1-5 PID parameter self-tuning 58
3-2 Typical multi-module control configuration 59
3-2-4 Communication Settings 59
3-2-5 The internal station address of the expansion module is automatically assigned 60
3-2-6 Module parameter setting 60
3-2-7 PID parameter auto-tuning 61
3-3 Typical multi-module control configuration 62
3-3-4 Communication Settings 63
3-3-5 Extension module internal station address automatic allocation 63
3-3-6 Module parameter setting 63
3-3-7 PID parameter auto-tuning 63
Chapter 4 Basic Parameter Description 64
4-1 Set input specifications 65
4-1-3 Input gain and offset (correction) 65
4-2 Set output specifications 68
4-2-1 Minimum output ON/OFF width (system internal parameter) 68
4-2-2 Operation volume upper limit / operation volume lower limit 68
4-2-3 Operating volume rising change limit / operating volume falling change limit 69
4-2-5 Current output lag time 69
4-3 Set control specifications 70
4-3-4 fixed output ( operated value ) 71
4-3-5 Heating and cooling dead zone 71
4-3-6 ON/OFF control deviation 71
4-4 Set LSP group parameters 73
4-5-2 set value ( SV value) 75
4-5-3 PID value description 75
4-8 Set RS485 communication station number 78
4-8-1 Station number display rule 78
Chapter 5 485 Communication Instructions 79
5-1 Overview of communication protocol 80
5-3 RS-485 communication specifications and protocol description 81
5-3-1 interface specifications 81
Chapter 6 Ethernet Communication Instructions 85
6-1 Ethernet communication specifications and protocol description 86
6-1-1 interface specifications 86
6-1-3 Ethernet communication settings 87
Chapter 7 Faults and Troubleshooting 88
7-2 Determine the error based on the indicator light 90
8-1 Appendix 1 : "Communication Function Code and Data Format" 92
8-1-1 Communication command function code 92
8-1-2 Detailed explanation of communication command function code 92
8-1-2-1 word data reading [Function code: 03 ] 92
8-1-2-2 Input register reading [Function code: 04 ] 93
8-1-2-3 Single function writing [Function code: 06 ] 93
8-1-2-4 Continuous function writing [Function code: 16 ] 94
8-2 Appendix 2 : "Register Parameter List" 95
8-2-2 Register parameter list 96
8-2-2-1 1#- 8# module parameter list 96
8-2-2-2 9#-16# module parameter list 98
8-2-2-3 Communication parameter list 100
8-2-2-4 CH1-CH8 channel parameter list 101
1# module ( CH1-CH8) channel parameters (parameter group 1 ) address definition: 101
1# module ( CH1-CH8) channel parameter (parameter group 2 ) address definition: 105
1# module ( CH1-CH8) channel parameters (parameter group 3 ) address definition: 109
1# module ( CH1-CH8) channel parameters (parameter group 5 ) address definition: 110
1# module ( CH1-CH8) channel parameters (parameter group 6 ) address definition: 116
User-defined data area (parameter group 7 ) address table: 120
8-2-3-5 Register storage content (current temperature value) 121
8-2-3-6 Register storage content (output operand) 122
8-2-3-7 Input register storage content (others) 123
8-3 Appendix 3 : " XD1N-ET8000 and Delta touch screen communication case" 125
8-3-1 RS 485 communication 125
8-3-2 Ethernet communication 131
8-4 Appendix 4 : " Communication between XD1N-ET8000 and Delta PLC " 137
8-5 Appendix 5 : " Sensor Types Supported by XD1N Series Temperature Control Module" 140
User manual
About this manual
About this manual
This manual describes the use of the XD1N multi-channel temperature control module , including the following chapters.
Try to install or operate
Please read this manual carefully and make sure you understand the contents before using the XD1N multi-channel temperature control module.
·Overview
Chapter 1 Overview describes the features of XD1N , names of each part, functions, label contents, and ordering information.
·Hardware and software introduction
Chapter 2 Preparation Work describes the preparation work required to use XD1N , including installation, wiring, use of debugging software, module upgrade and other information.
·Typical application examples
Chapter 3 Typical Control Examples describes the basic application of XD1N (software usage, parameter setting, monitoring and debugging) with specific control examples.
·Basic parameter setting instructions
Chapter 4: XD1N basic unit function parameter setting instructions.
· RS485 communication instructions
Chapter 5 RS485 Communication Description describes the XD1N module M0DBUS RS485 communication protocol specifications.
· Ethernet communication instructions
Chapter 6 Ethernet Communication Description describes the XD1N module M0DBUS TCP/IP communication protocol specifications.
·troubleshooting
Chapter 7 Troubleshooting describes solutions to possible problems that may arise in checking operation based on the classification of the temperature control module status.
·Parameter list and communication cases
The appendix of Chapter 8 provides parameter list, status list, module address details, communication cases with the host computer and other information.
User manual
Chapter 1 Overview
Chapter 1
Overview
This chapter mainly introduces the characteristics, professional terms and functions of the XD1N series temperature control module.
1-2-2 indicator light definition 14
1-3 I/O configuration and main functions 15
User manual
1-1 Product Overview
The XD1N series single module provides 4/8 channels of sensor input, which can simultaneously measure 4/8 different temperatures and control 4/8 outputs .
The XD1N series includes: host module, expansion module. One XD1N host can be connected to up to 15 expansion modules, and can perform up to 128 channels of temperature control. With RS485 or Ethernet , multiple XD1N hosts can be connected to achieve temperature control of up to a thousand points.
1-1-1 product features
The XD1N series is a multi-channel modular temperature controller. The modular design is convenient for users to apply and install. The host collects information from each expansion module and the channels are completely isolated, which can improve the stability of measurement.
• A single host module can control the temperature of 4/8 channels .
• A single host module can be expanded with 15 expansion unit modules.
• The terminal block can be removed and connected.
• The host module supports RS485 and Ethernet communication.
• Modular design simplifies wiring installation.
• Complete isolation between channels.
• The host module collects expansion module information to improve information exchange efficiency.
User manual
1-2 Part name
1-2-1 appearance interface
| ||
| | |
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
|
|
| ||
| | |
|
| |
|
| |
|
| |
|
| |
|
| |
|
| |
User manual
1-2-2 indicator light definition
| | |
PWR | | |
RUN | | |
ERR | | |
485 | |
|
NET | | |
| | |
User manual
1-3 I/O configuration and main functions
1-3-1 I/O configuration
1-3-2 Main functions
• The main input channels CH1-CH8 of a single module are temperature sampling input ports.
• The control outputs CH1-CH8 of a single module are temperature control output ports, corresponding to the main input CH1-CH8 .
• A single host module can be expanded with 15 expansion modules through the inter-module communication interface .
• The terminal block can be removed and connected.
User manual
1-3-3 Electrical indicators
|
|
|
|
|
|
|
|
| |
| |
| |
| 500MS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| |
|
|
|
|
|
|
|
|
User manual
1-4 label description
User manual
1-5 Purchase information
XD | _N | - | E | T | 8 | 0 | 0 | 0 |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
1 |
|
2 |
|
3 |
|
4 |
|
5 |
|
6 |
|
7 |
|
8 |
|
9 |
|
1-5-1 Ordering Guide (Example)
| |
|
|
|
| XD1N-ET8000 |
| PT | 8 |
| XD1N-ET8100 |
| TC | 8 |
|
|
| PT | 8 |
|
|
| TC | 8 |
Note:
( 1 ) The expansion module does not have an external 24V power input terminal and cannot be used alone.
( 2 ) Please pay attention to the manufacturer’s official website announcement for model updates.
User manual
Chapter 2 Hardware and Software Introduction
Chapter 2
Hardware and software introduction
This chapter mainly introduces the preparation work, installation, wiring and station address setting, connection monitoring, parameter setting, etc. required for using XD1N .
Chapter 2 Hardware and Software Introduction 19
2-3-1 Operating environment 23
2-3-2 Software installation 23
2-4-3 Communication settings 27
2-4-3-1 RS485 communication parameter setting 27
2-4-3-2 Ethernet communication parameter setting 29
2-5 Expansion module internal communication station address automatic allocation 32
2-7-2 Basic parameter setting 39
2-7-5 Control parameter setting 42
2-7-6 LSP group parameter setting 43
2-7-7 PID group parameter setting 44
2-7-10 RS485 communication station number setting 48
2-7-10-1 RS485 communication station number 48
User manual
2-1Hardware installation
2-1-1 Dimensional unit ( mm)
|
|
|
|
User manual
2-2 terminal arrangement
8- channel host module:
PT series TC series
8-channel expansion module:
PT series TC series
User manual
4- channel host module
PT series TC series
4- channel expansion module
PT series TC series
User manual
2-3 Software installation
The software is used for XD1N series temperature control module parameter setting, monitoring and debugging, and supports Ethernet and RS485.
Communication connection.
2-3-1 Operating environment
1 , 2 , 3... The following configuration is recommended for the running and installation environment of the host computer software:
1.OS :
Windows 7 [32bit or 64bit] or above
2. CPU : 1GHz or above
3. Memory environment: 1[GB] or more
4.Display
Compatible with Windows displays with a resolution of XGA (1024 × 768 [pixel]) or above.
5.Hard disk
Hard drive space capacity of 100[MB] or more.
2-3-2 Software installation
1 , 2 , 3... 1. Start the XD-SDP installer
Double click - XD-SDP_S tandard_ Setup -***.msi
Figure 2.2.1
2. Display the installation preparation screen
Confirm the installation of [ XD-SDP ] and click [Next]
User manual
3. Sign the use commitment letter
When using this software, please pay attention to the content of the use commitment letter and read it carefully.
If there are no problems, click [Agree] and then click [Next]
4. Follow the prompts to complete the installation.
Click the [Close] button to complete the installation.
User manual
2-4 Software connection
Debugging Guide
User manual
2-4-1 Enter the project
1 , 2 , 3... 1. Double-click on the desktop to start [ SD-SDP.exe ], and the following dialog box will pop up. Please choose different ways to enter the project.
1.1 New construction
Click [New Project] and [OK] to create a new project.
1.2 Select existing projects
Click [Select an existing project] and [OK] to import the previously created and saved project, as shown below:
1.3Default last project
Click [Default last project] and click the [OK] button to read the project saved when XD-SDP was closed last time.
and enter.
User manual
2-4-2Initial settings
After entering as [New Project], you need to configure the temperature control module and perform initial parameter settings.
Can communicate with the temperature control module. Entering in the other two ways will automatically import the previous project configuration, and you can directly
Please skip this section.
2.1 Add and delete modules
Open the XD-SDP software and when creating a new project, the system default setting is module 1, and the module name is customized.
After entering the main project screen, click [Options] - [Add and Delete Modules] in the menu bar to enter the Add and Delete Modules screen.
As shown below:
In this screen, you can add / delete modules, and rename / modify notes on existing modules.
do.
2-4-3 Communication settings
Please choose different communication connection methods according to the networking method :
( 1 ) RS -485 communication parameter setting
( 2 ) Ethernet communication parameter setting
Purpose: Use SD-SDP debugging software to establish a communication connection with the module through a personal computer.
Set the communication parameters through [Options] - [Communication Settings ] to establish a connection between the module and the PC- side SD-SDP software.
2-4-3-1 RS485 communication parameter setting
1 , 2 , 3... 1. Select the device you want to connect in the left area of the main screen, as shown in the figure below:
User manual
2. Enter the communication setting screen through [Options] - [Communication Settings ] , as shown in the figure below:
3. In the communication setting screen, select the tab [RS-485] and set the properties of the required connected device.
As shown below:
4. After the setting is completed, you can click the [Connection Test] button to test whether the parameters are set correctly. If it prompts "Connection Test"
"Try successful" means that the connection can be established normally, as shown in the following figure: (This step can be omitted)
5. Click the [OK] button to save the current settings. After returning to the main screen, select the module and right-click
[Connect] to establish the current connection, as shown in the figure below:
User manual
2-4-3-2 Ethernet communication parameter setting
There are two descriptions for new modules and already set modules:
1. New modules:
In order to establish a connection between the new temperature control module and the PC-side SD-SDP software for monitoring and debugging,
In [Module 1]-[ Options] - [Communication Settings ] - [ E thernet ] - [ IP Search ] the following address:
|
|
|
| 192.168.0.3 |
|
| 1024 |
2. Modules have been set:
Then use the IP search function to check the IP address of the module and establish a connection with the PC .
1 , 2 , 3.... 1. Set the IP address of the PC : such as 192.168.0.2 or other addresses. Make sure it is in the same network segment as the module IP .
Select the device you want to connect to in the left area of the main screen, as shown in the figure below:
3. Enter the communication setting screen through [Options] - [Communication Settings ] , as shown in the figure below:
4. In the communication setting screen, select the label [ Ethernet ], as shown in the figure below:
User manual
5. Click the [ IP Search ] button, as shown in the figure below:
6. Click [Refresh List], select the corresponding network card, and then click the [Search] button, as shown in the figure below:
7. After the search is completed, select the object and click the [OK] button, as shown in the figure below:
8. You can click the [Connection Test] button to test whether the parameters are set correctly. If it prompts "Connection Test"
"Successful" means that the connection can be established normally. As shown in the figure below: (This step can be omitted)
9Click the [OK] button to save the current settings. After returning to the main screen, select the module and right-click
[Connect] to establish the current connection, as shown in the figure below:
Remark
( 1 ) The purpose of [ IP Search] in [Options] - [Communication Settings ] is to read the module IP and establish a connection with the PC .
( 2 ) The IP address assigned to the module in the project needs to be set in [Module] - [Communication Settings] after the module has established a connection with the PC . For details, please refer to " 2-7 Parameter Settings 2-7-11 " "Ethernet IP address settings are explained".
2-5 Expansion module internal communication station address automatic allocation
This temperature control module provides the function of automatically assigning internal communication station addresses to expansion modules connected to the host module.
Before performing address assignment settings, please cut off the power supply, securely connect the expansion module hardware, and then turn on the power again.
( 1 ) The expansion module does not support hot insertion and removal. Please do not add or replace modules while the power is on.
( 2 ) When the host module is connected to multiple expansion modules, it is recommended to terminate the internal communication of the last expansion module.
Set the DIP switch of the terminal resistor to the [ ON ] position (the factory default is [ OFF ]).
(3)
Or more than two expansion module DIP switches are in the [ ON ] position, which will cause the communication to operate abnormally .
The automatic allocation operation is as follows:
1 , 2 , 3... 1. After operating 2-4 communication settings and successfully connecting to the PC , select the module, click [Options] - [ Set Slave Address ], [Auto Number] to set the current The expansion modules of each module in the project automatically assign communication station addresses.
The operation steps are shown in the figure below:
2. Click [Auto Number], as shown in the figure below:
3. After the automatic address allocation is completed, the internal station addresses of all expansion modules under the module will be automatically updated and established.
connect .
User manual
Remark:
( 1 ) If there are multiple modules, each module needs to perform the [Automatic Numbering] step once.
( 2 ) During the execution of [Automatic Numbering], the expansion module output indicator light performs a ticker action.
( 3 ) After the current module [automatic numbering] operation is successful, the internal communication station address is automatically assigned to the expansion module.
( 4 ) If the modules in the project are replaced (host module, or expansion module) or automatically numbered successfully
If the modules in the module change their positions, the [Automatic Numbering] step must be performed again for the module.
( 5 ) After this step is successfully executed, you can debug, monitor and set parameters for the expansion module in the module.
User manual
2-6 connection monitoring
The monitoring screen is also the main screen of this software. Execute " 2-4 Communication Settings", " 2-5 Expansion Module Internal Station Location"
After the "Address Automatic Numbering" is successful, click [Monitoring Screen] - [Module] - [Module] in the left area and then click the upper right
Click the [Connect] button in the corner to enter the monitoring and debugging state, as shown in the following figure:
2-6-1 real-time data
After connection, the screen can display real-time [PV value], [SV value], [proportional band], [integration time],
[ Differential time ], [ Operation volume ] and other information . As shown in the picture:
Operation command:
( 1 ) Click the [Start / Stop] switch and the auto-tuning [Start / Stop] switch to change the start/stop or auto-tuning status of the current channel.
( 2 ) Double-click the [ SV Value ], [ Proportional Band ], [ Integral Time ], and [ Derivative Time ] labels to change the setting parameters of the current channel .
User manual
2-6-2 Dynamic trends
This screen can display the dynamic trend of temperature collected by 8 channels , as shown in the figure:
1 ) Double-click the color label to modify the color of the selected channel.
2 ) Click [Auto Adjust] to zoom the screen to the optimal ratio.
3 ) Click [Save to local] to save the screen to local, which can be viewed in [Options] - [ View historical curve ]
View the saved footage .
4) Support operations:
Scroll wheel: Zoom in and out of the timeline .
Ctrl+ Scroll Wheel: Scale the temperature axis .
Mouse drag: move the current graphic .
Mouseover: Displays the temperature and time at the hovered location .
User manual
2-6-3 Alarm
This screen displays the abnormal conditions of each module in the project, as shown in the figure:
User manual
2-6-4 View historical data
Click [Options] - [View Historical Curve] in the menu bar to enter the historical curve screen, as shown in the figure:
After exporting the dynamic trend curve of the monitoring screen, import it into the screen.
Supported operations:
Scroll wheel: Zoom in and out of the timeline .
Ctrl+ Scroll Wheel: Scale the temperature axis .
Mouse drag : move the current graphic .
Mouseover: Displays the temperature and time at the hovered location .
User manual
2-7 Parameter setting
2-7-1 Function description
Click [Export Parameters] on the lower right to export the parameters in the software to an external file.
Click [Import Settings] on the lower right to import the exported parameters into the software.
Click [Read Settings] on the lower right to read the module's setting parameters from the module.
Click [Write Settings] on the lower right to write the module's setting parameters into the module.
Click [Restore Default Parameters] in the lower right corner to restore the module's setting parameters to their initial values.
Click [Calibrate Sensor] on the lower right to automatically calculate the bias and gain through the two-point method.
Click [Set Mapping Address] on the lower right to set the mapping address of the module.
Click Help on the lower right to view the analysis of the current setting screen.
Follow the steps below to set parameters:
1 , 2 , 3.... 1. Change the parameters that need to be modified or the content that needs to be operated.
2. Click the [Confirm] button. If there is any abnormality in the set data, a prompt will appear.
3. Click [Confirm] and then click [Write Settings] to indicate that the modified parameters are written to the module and the parameter modification is completed.
Remark
( 1 ) The communication parameter is the IP address assigned to the temperature control module in the project .
For example: In the entire project, the IP assigned to this temperature control module is: 192.168.0.15
Then enter 192.168.0.15 in [Setting Screen] - [Module] - [Set Communication Parameters] . If there is
For multiple modules, enter the corresponding IP address for each module.
( 2 ) After the communication parameter setting of the module is completed, the communication content in the software’s [Options] - [Communication Settings]
Automatically update the content in [Set Communication Parameters] to maintain a real-time connection between the current module and the PC XD-SDP software.
Automatically update the content in [Set Communication Parameters ] to maintain a real-time connection between the current module and the PC XD-SDP software.
User manual
2-7-2 Basic parameter setting
Data valid range:
Autorun : valid / invalid
Delayed start : 0~600
User manual
2-7- 3 Input settings
Data valid range:
Valid channels : valid / invalid
Sensor : supports PT , TC , all-pass
Gain : 0.000~10.000
Offset: -10.0~10.0
Filter factor 1 : 0~30
Filter factor 2 : 0~30
Filter factor 3 : 0~30
User manual
2-7- 4 Output Settings
Data valid range:
Control mode: 0: heating 1: cooling
Output upper limit: 0.0~100.0
Output lower limit : 0.0 ~ 100.0
Control mode: PID / fixed operating value / 【 ON/OFF 】
Fixed operation amount : 0~100
User manual
2-7- 5 Control parameter setting
Data valid range:
System type: 0 : Standard, 1 : Fast response
Control mode: heating, cooling, heating/cooling
Control cycle : 1 00~ 1 0000
Operation mode: fixed value / PID, fixed output, ON /OFF, ramp operation, cascade control, block control
Fixed output : 0.0~100.0%
Heating and cooling dead zone: - 3200.0~3200.0
ON/OFF control deviation: - 3200.0~3200.0
LSP group number: 0~8
Ramp up slope: 0 -32000
Ramp down slope: 0 -32000
Ramp units: 0 : 0.1 seconds , 1 : 1 minute, 2 : 1 hour
User manual
2-7- 6 L SP group parameter setting
Data valid range:
LSP1 SP:-300.0~3000.0℃
LSP1 PID group number: PID1 group 1-PID8 group
User manual
2-7- 7 PID group parameter setting
Data valid range:
Proportional band: 0.0 ~999.9
Points band: 0.0 ~99.9
Differential band: 0.0 ~999.9
User manual
2-7- 8 Alarm settings
Provides two alarm contents [Alarm 1 ] and [Alarm 2 ] . The valid data range of each alarm is as follows
Data valid range:
Alarm 1 mode: 0~6
Alarm 1 function: 0~2
.Alarm 1 delay : 0~100 s
Alarm 1 upper limit : -300.0~3000.0 ℃
Alarm 1 lower limit : -300.0~3000.0 ℃
Alarm 2 mode: 0~6
Alarm 2 function: 0~2
.Alarm 2 delay : 0~100 s
Alarm 2 upper limit : -300.0~3000.0 ℃
Alarm 2 lower limit : -300.0~3000.0 ℃
User manual
2-7- 9 Set address mapping
In order to make it easier for customers to read and write data, this product provides an address mapping function. The user-defined data area is opened to customers, which is used to turn discontinuous parameter addresses into continuous addresses. The data length is 1024 addresses .
The mapping area is from 0X1C00-0X1FF0 , with a total of 1024 addresses .
Operation steps:
1 , 2 , 3.... 1. After the current module has established a connection with the PC , select the module to be set in the area setting interface on the left.
As shown below:
2. Hold down [ Shift ] on the computer - click [Set Mapping Address] to enter the custom mapping address screen , as shown in the figure below:
3. Click [View Parameters] to enter the mapping address editing screen , as shown in the figure below:
The mapping area is from 0X1C00-0X1FF0 , with a total of 1024 addresses. There are 16 addresses in a single row in the software mapping address table.
Setting method:
Please choose two different setting methods according to customer habits:
( 1 ) Press [Export Parameters] to export an EXCEL file, and edit the addresses that need to be mapped in the EXCEL table.
After checking, click [Import Parameters] to import the EXCEL file into the software to complete the address mapping .
settings.
( 2 ) In the mapping address table of this interface, manually enter the address that needs to be mapped, and click the [OK] button.
Note: ( 1 ) Please read the instructions carefully before setting.
( 2 ) The mapped address is stored in the host module. When replacing the host module, the mapped address needs to be re-imported or
Enter it manually once.
( 3 ) It is recommended that customers export parameters and save the EXCEL file after completing debugging .
User manual
2-7- 10 R S485 communication station number setting
When the client host computer communicates with multiple modules through RS485 , it is necessary to set the RS485 station number of the host module in each module .
Otherwise, communication connections cannot be established with each module, and duplicate or incorrect settings will cause errors in reading and writing data from the host computer.
Set communication parameters through [Options] - [Communication Settings ].
2-7-10-1 RS485 communication station number
Set the station number to 1 , 2 , 3...1. During use, the module in the general electric control cabinet has been installed, and the input and output lines on the module, the RS485 communication line and the host computer have also been connected. It is troublesome to remove the communication line from the host module and then use the 485 port to connect to the computer to set the station number. Therefore, it is recommended to use the Ethernet port to set the RS485 station number of each module host module.
Station number [display] 2. After the host module station number of each module is set one by one, check whether the station number of all modules is set correctly.
Switch to the RS485 communication setting interface, click [Display Station Number] - [Display], and the indicator light status of each module host module on the 4 85 link switches to the RS 4 85 station number display mode.
User manual
Set the purpose of this function:
When all station numbers are set, it is convenient for customers to check whether all RS485 station numbers are set correctly through the status of the indicator lights on the panel .
Station number [do not display]
3. Click [Show station number] - [Do not display], and the indicator light status of each module host module on the 4 85 link switches back to output.
Display mode.
Note: During normal operation, the indicator light status is in the output display mode. After operating the station number [display] function, when the verification is completed
After all station numbers are set without errors, you must operate the station number [not displayed] or power off the host modules of all modules and restart them.
times, let the indicator light status switch to output display mode.
Remark
( 1 ) The rules for the indicator light to display the station number. For details, please refer to the instructions in " 4-8 Setting the RS 4 85 Communication Station Number".
User manual
2-7- 11 Ethernet IP address setting
Purpose : Set the IP address of the module in the project .
The IP address assigned to the module in the project needs to be set in [Module] - [Communication Settings] after the current module has established a connection with the PC .
1 , 2 , 3.... 1. After the current module has established a connection with the PC , select the connected module in the left area, as shown in the figure below:
3. Enter the communication setting screen through [Options] - [Communication Settings ] , as shown in the figure below:
4. In the communication setting screen, select the tab [ Ethernet ], enter the IP address , and click [Write].
User manual
2-7-12 Slope control
Overview of slope control
Control the temperature according to the set slope.
Original SV : original set temperature value, new SV: new set temperature value
How to set slope control
|
|
|
|
|
|
| 0-32000 | 0 |
|
| 0-32000 | 0 |
| |
|
| 0 |
Slope setting example:
For example: the original set value is 3 0 , the new set temperature value is 1 00 , the ramp up slope is set to 1000 , the ramp unit
Set to 0 (unit: seconds)
It means that the time it takes to rise from the original set temperature of 30 degrees to the target temperature of 100 degrees is 1000 seconds .
User manual
2-8 Exception prompts